NT-303 · NT-304
NT-303 · NT-304 is a LoRaWAN room thermostat for 2- and 4-pipe fan coils. NT-303 drives on/off valves and a 3-speed fan through 5 relays; NT-304 drives 0–10 V valves or an EC fan through 3 relays and 2 × 0–10 V outputs. The 2.7″ E-ink screen shows temperature, humidity, target temperature and mode; temperature and humidity sensors are built in, with an NTC sensor input and an input for a keycard switch or window sensor. The thermostat stores 8 schedule plans, provides freeze protection and works in LoRaWAN Class C, so it accepts commands at any time, including group commands via multicast. It is powered from 100…240 V AC mains and configured via NFC from a smartphone and by downlink commands.
The form failed to load — write to info@orion-m2m.com
Features
- For 2- and 4-pipe fan coils: relay or 0–10 V outputs;
- 2.7″ E-ink screen: temperature, humidity, target temperature and mode;
- Temperature and humidity sensors, NTC sensor input;
- Input for a keycard switch or window sensor;
- 8 schedule plans, freeze protection;
- Configuration via NFC from a smartphone and by downlink commands;
- Applications: remote climate control via LoRaWAN, replacing wired fan coil controllers, group control via multicast, energy saving with keycard and open-window detection.
Specifications
LoRaWAN regional plans: EU868 · IN865
General
| Screen | 2.7″ E-ink, black and white |
|---|---|
| Control buttons | 5 |
| Configuration | NFC, downlink |
| Mains supply, 50…60 Hz | 100 … 240 V AC |
| Power consumption, no load, W | < 2 |
| Operating temperature: device · screen, °C | −20 … +60 · 0 … +40 |
| Humidity, non-condensing, % | 0 … 95 |
| Housing, protection | PC + ABS, white, UL94 V0, IP20 |
| Dimensions, mm | 86 × 86 × 42 |
| Wall box: square / round, mm | 86 / 60 |
| Wire cross-section, mm² | 0.13 … 2.08 (AWG 26…14) |
Measurement
| Temperature: range · resolution, °C | −20 … +60 · 0.1 |
|---|---|
| Temperature accuracy, °C | ±0.5 (0…+60 °C) / ±1 (−20…0 °C) |
| Humidity: range · resolution, % RH | 0 … 100 · 0.1 |
| Humidity accuracy: typ. / max, % RH | ±2 / ±5 |
Fan coil control
| NT-303 outputs | 5 relays: on/off valves, 3-speed fan |
|---|---|
| NT-304 outputs | 3 relays and 2 × 0–10 V: 0–10 V valves or EC fan |
| 2-pipe, 2- or 3-wire on/off valve | 3-speed fan — NT-303; EC fan 0–10 V — NT-304 |
| 2-pipe, 0–10 V valve | NT-304 with either fan |
| 4-pipe, 2 × 2-wire on/off valves | 3-speed fan — NT-303; EC fan 0–10 V — NT-304 |
| 4-pipe, 2 × 0–10 V valves | NT-304 with a 3-speed fan |
| Relay current: resistive / inductive, A | 4 / 3 |
| Target temperature, °C | 5 … 35, step 0.5 or 1 |
| Modes | heating, cooling, ventilation |
| Inputs | 1 NTC, 1 dry contact (DI) |
LoRaWAN
| Specification version | 1.0.2 / 1.0.3 |
|---|---|
| Class, activation | Class C, OTAA / ABP |
| Tx power (868 MHz), dBm | 16 |
| Sensitivity, dBm | −137 |
| Antenna | internal |
| Reporting interval, min | 1 … 1440 (default 10) |
Supply
| Package contents | thermostat, 2 × M4×25 screws, M2×4 locking screw, DI input signal cable, product passport, warranty card |
|---|
Documentation
Datasheets
Versions
| Part number | Version |
|---|---|
| NT-303/[F] | 5 relays: on/off valves, 3-speed fan. |
| NT-304/[F] | 3 relays and 2 × 0–10 V outputs: 0–10 V valves or EC fan. |
Need a solution for your project?
Contact us: we will select the equipment and network architecture to fit your requirements
Contact us