OrionM2M
MUSE

MUSE

MUSE is a LoRaWAN module for fan coils and air conditioners. It connects to the unit’s own controller: MUSE-U to the port of the built-in Wi-Fi module and is powered from it, MUSE-R to the RS-485 bus with external power. The module reports mode, setpoint, temperature and faults and, on server commands, switches the unit on and off and changes the mode, setpoint and fan speed. LoRaWAN Class C receives commands at any time, so a building’s fan coils can be brought into BMS without bus wiring. Compatible brands and models are listed in the datasheet.

Features

  • MUSE-U: powered from the unit’s port, no power supply or wiring;
  • Reports mode, setpoint, temperature and faults;
  • Accepts commands: on/off, mode, setpoint, fan speed;
  • LoRaWAN Class C: server commands received at any time;
  • Software-selectable 3.3 / 5 V logic levels and line direction;
  • BMS integration without RS-485 bus wiring;
  • Applications: building-wide fan coil and AC monitoring, retrofits without new cabling, centralized mode and setpoint control, equipment fault monitoring.

Specifications

LoRaWAN regional plans: EU868 · IN865

Interfaces

MUSE-U interface UART, 4 lines: TX, RX, IO1, IO2
Direction, per line input or output, by software
Line logic level, V 3.3 / 5, by software
TX / RX swap, inversion by software
Baud rate, baud 2400 … 115,200
MUSE-R interface RS-485, point-to-point
Termination, Ω 120, switchable

Power and construction

Supply voltage, nominal, V DC 5 / 12 / 24
Supply voltage range, V DC 4.5 … 26.4
Operating temperature, °C −10 … +60
Housing ABS, white, UL94 HB
Housing dimensions, mm 75 × 35 × 12
Length incl. cable gland, mm 90
MUSE-U cable length, m 0.7
Service mode entry by magnet
Mounting inside the fan coil or air conditioner

LoRaWAN

Specification version 1.0.3
Class, activation Class C, OTAA
Tx power, dBm up to 14
Sensitivity (SF12), dBm −136
ADR, encryption yes, AES-128
Antenna internal, PCB
Radio platform STM32WLE5

Data and control

Reported data mode, setpoint, temperature, faults
Commands on/off, mode, setpoint, fan speed
Indicators PWR — power, JOINED — joined LoRaWAN, ACT — activity, LINK — unit communication
Package contents module, connection cable

Documentation

Datasheets

Versions

Part number Version
MUSE-U/[F] UART to the unit’s Wi-Fi module port, port-powered; 0.7 m connection cable.
MUSE-R/[F] RS-485, external power 5 / 12 / 24 V DC, 120 Ω termination.

Need a solution for your project?

Contact us: we will select the equipment and network architecture to fit your requirements

Contact us