NEM-6L24 is a three-phase energy submetering module for DIN-rail mounting with external current transformers up to 100 A. It measures voltage, current, active, reactive and apparent power, power factor, frequency and energy per phase with accuracy class 1 % and delivers the data over Modbus-RTU via RS-485 or UART TTL with galvanic isolation. Any Modbus master can poll it: a PLC, a BMS or SCADA controller, a PC or a gateway. The module is used for energy submetering of HVAC and ventilation units, measurement and verification of energy savings, BMS and SCADA integration and retrofits of existing switchboards.
The form failed to load — write to info@orion-m2m.com
Features
- Per-phase measurement: U, I, P / Q / S, PF, frequency, energy;
- Accuracy class 1 % across all measured values;
- Modbus-RTU over RS-485 and UART TTL, galvanically isolated;
- External CTs up to 100 A — solid-core or split-core;
- Ultra-low self-consumption — 0.3 W typ., powered from the mains;
- Non-volatile energy counters up to 399,999,999.9 kWh;
- Applications: energy submetering of HVAC and ventilation units, measurement and verification of energy savings, BMS / SCADA integration, retrofits of existing switchboards.
Specifications
General
| Wiring | three-phase, 3- or 4-wire |
|---|---|
| Voltage range, V | 50 … 566 |
| Nominal voltage, V | 220 / 380 |
| Current range, A | 0 … 100, via external CTs |
| Line frequency, Hz | 45 … 65 |
| Accuracy class, % | 1 |
| Self-consumption, W | 0.3 typ. / 2 max. |
| Operating temperature, °C | −20 … +60 |
| Dimensions, mm | 116 × 76 × 27.8 |
| Mounting | 35 mm DIN rail |
| Weight, g | 107 (PCB 51) |
Outputs and isolation
| CF pulse output | open drain, 10 ms pulse, 1000 imp/kWh |
|---|---|
| RS-485 / UART isolation | galvanic |
| Current inputs | 3 external CTs, solid-core or split-core |
| Voltage inputs | L1, L2, L3, N |
Measurement
| Power P / Q / S per phase | 0 … 38 kW / kvar / kVA |
|---|---|
| Power factor | 0 … 1, resolution 0.01 |
| Active energy, kWh | up to 399,999,999.9 |
| Reactive and apparent energy | kvarh and kVAh |
| Phase angles | 0 … 360°, resolution 0.01° |
Communication and addressing
| Protocol | Modbus-RTU, 8N1 + CRC-16 |
|---|---|
| Interfaces | RS-485 and UART TTL (3.3 / 5 V) |
| Baud rate, bit/s | 2400 … 115,200 (default 9600) |
| Address | 1 … 247 (default 1), by DIP switch or software |
| Reference / maximum current, A | Ib 10 / Imax 100 |
| Line frequency, selectable | 50 or 60 Hz |
Documentation
Datasheets
Versions
| Part number | Version |
|---|---|
| NEM-6L24-100C | Kit of 3 solid-core CTs, 100 A. |
| NEM-6L24-100S | Kit of 3 split-core (clamp-on) CTs, 100 A. |
Need a solution for your project?