OrionM2M
NEM-6L24

NEM-6L24

NEM-6L24 is a three-phase energy submetering module for DIN-rail mounting with external current transformers up to 100 A. It measures voltage, current, active, reactive and apparent power, power factor, frequency and energy per phase with accuracy class 1 % and delivers the data over Modbus-RTU via RS-485 or UART TTL with galvanic isolation. Any Modbus master can poll it: a PLC, a BMS or SCADA controller, a PC or a gateway. The module is used for energy submetering of HVAC and ventilation units, measurement and verification of energy savings, BMS and SCADA integration and retrofits of existing switchboards.

Features

  • Per-phase measurement: U, I, P / Q / S, PF, frequency, energy;
  • Accuracy class 1 % across all measured values;
  • Modbus-RTU over RS-485 and UART TTL, galvanically isolated;
  • External CTs up to 100 A — solid-core or split-core;
  • Ultra-low self-consumption — 0.3 W typ., powered from the mains;
  • Non-volatile energy counters up to 399,999,999.9 kWh;
  • Applications: energy submetering of HVAC and ventilation units, measurement and verification of energy savings, BMS / SCADA integration, retrofits of existing switchboards.

Specifications

General

Wiring three-phase, 3- or 4-wire
Voltage range, V 50 … 566
Nominal voltage, V 220 / 380
Current range, A 0 … 100, via external CTs
Line frequency, Hz 45 … 65
Accuracy class, % 1
Self-consumption, W 0.3 typ. / 2 max.
Operating temperature, °C −20 … +60
Dimensions, mm 116 × 76 × 27.8
Mounting 35 mm DIN rail
Weight, g 107 (PCB 51)

Outputs and isolation

CF pulse output open drain, 10 ms pulse, 1000 imp/kWh
RS-485 / UART isolation galvanic
Current inputs 3 external CTs, solid-core or split-core
Voltage inputs L1, L2, L3, N

Measurement

Power P / Q / S per phase 0 … 38 kW / kvar / kVA
Power factor 0 … 1, resolution 0.01
Active energy, kWh up to 399,999,999.9
Reactive and apparent energy kvarh and kVAh
Phase angles 0 … 360°, resolution 0.01°

Communication and addressing

Protocol Modbus-RTU, 8N1 + CRC-16
Interfaces RS-485 and UART TTL (3.3 / 5 V)
Baud rate, bit/s 2400 … 115,200 (default 9600)
Address 1 … 247 (default 1), by DIP switch or software
Reference / maximum current, A Ib 10 / Imax 100
Line frequency, selectable 50 or 60 Hz

Documentation

Datasheets

Versions

Part number Version
NEM-6L24-100C Kit of 3 solid-core CTs, 100 A.
NEM-6L24-100S Kit of 3 split-core (clamp-on) CTs, 100 A.

Need a solution for your project?

Contact us: we will select the equipment and network architecture to fit your requirements