NDW210
NDW210 is a multi-circuit power meter for DIN-rail mounting: one meter covers up to 4 three-phase circuits with split-core CTs up to 600 A included or with the customer’s x/5 CTs. For each circuit it measures voltage, current, active, reactive and apparent power, power factor, frequency, phase angles, unbalance and harmonics up to the 31st, counts energy in 4 quadrants across 4 rates and keeps a 12-month and 31-day history. Accuracy class is 0.5 for voltage and current and 1 for active energy. Data is delivered over RS-485, Modbus-RTU; any Modbus master can poll it: a PLC, a BMS controller, SCADA or a PC. The built-in 2 DI and 2 relay DO report breaker status and control breakers, while the NDW-MK (12 DI + 4 DO) and NDW-TL (12 NTC + 4 leakage current inputs) modules add inputs, outputs, temperature and leakage current monitoring in the panel.
The form failed to load — write to info@orion-m2m.com
Features
- Up to 4 three-phase circuits per meter: split-core CTs up to 600 A included, or connection to x/5 CTs;
- Measurement: U, I, P / Q / S, PF, frequency, phase angles, unbalance, harmonics 2 … 31;
- Accuracy class: U and I 0.5, active energy 1, reactive energy 2;
- 4-quadrant energy, 4 rates, 12-month and 31-day history;
- 2 digital inputs and 2 relay outputs: alarm setpoints, 200-record event log;
- RJ45 expansion modules: NDW-MK (12 DI + 4 DO) and NDW-TL (12 NTC + 4 leakage current inputs);
- Applications: per-feeder metering in main and distribution switchboards, power quality and harmonics monitoring, breaker status and remote control, temperature and leakage current in panels.
Specifications
General
| Wiring | three-phase, 4-wire or 3-wire (3P4W / 3P3W) |
|---|---|
| Current circuits | 1 … 4 three-phase (versions 1S … 4S) |
| Rated voltage, V | 3 × 220 / 380 AC |
| Rated current with supplied CTs, A | 100 / 400 / 600 (D16 / D24 / D36) |
| Rated current for x/5 CTs, A | 5 (D10) |
| Mains frequency, Hz | 45 … 65 |
| Auxiliary power, V | AC/DC 85 … 265 |
| Power consumption, VA | ≤ 10 |
| Operating temperature, °C | −20 … +60 |
| Relative humidity, % | ≤ 95 |
| Dimensions (H × W × D), mm | 87.8 × 72 × 71.5 |
| Mounting | 35 mm DIN rail |
Measurement and accuracy
| Measured values | U, I, P / Q / S, PF, frequency, phase angles, U and I unbalance, THD, harmonics 2 … 31 |
|---|---|
| Accuracy class: voltage, current | 0.5 |
| Accuracy class: active / reactive energy | 1 / 2 |
| Frequency error, Hz | 0.05 |
| Harmonics 2 … 31 error, % | ±1 |
| Energy metering | 4 quadrants, 4 rates |
| Energy history | 12 months, 31 days |
| Demand I and P | maximum and real-time |
| Event log | 200 records |
I/O and communication
| Digital inputs (DI) | 2, dry contact, built-in supply |
|---|---|
| Relay outputs (DO) | 2, normally open contact |
| DO rating, A | 3 at AC 250 V or DC 30 V |
| Pulse output | optocoupler, open collector |
| Interface and protocol | RS-485, Modbus-RTU (read FC 0x03) |
| Baud rate | 1200 … 38,400 (default 9600) |
| Frame format | N81, E81, O81, N82 (default N81) |
| Address | 1 … 247 (default 1) |
| Line termination, Ω | 120 |
Expansion modules
| NDW-MK (suffix -MK) | 12 DI (dry contact, built-in supply) + 4 DO (relay, normally open contact, 3 A at AC 250 V or DC 30 V) |
|---|---|
| NDW-TL (suffix -TL) | 12 NTC (−20 … +100 °C, ±2 °C) + 4 leakage current inputs (10 … 3000 mA, 1.0 %) |
| Leakage CT NDW-LCT45 | 45 mm window, class 1, one per NDW-TL channel |
| Module connection | RJ45: DC 12 V and Modbus-RTU from the meter; up to one module of each type |
| Module consumption, W | ≤ 1 |
Documentation
Datasheets
Versions
| Part number | Version |
|---|---|
| NDW210-D16-[S] | Split-core CTs 100 A included, 16 × 17 mm window; S — number of circuits, 1S … 4S. |
| NDW210-D24-[S] | Split-core CTs 400 A included, 24 × 23.5 mm window. |
| NDW210-D36-[S] | Split-core CTs 600 A included, 33.5 × 35 mm window. |
| NDW210-D10-[S] | CTs 5 A (Ø10) included — for the customer’s x/5 CT secondaries. |
| NDW-MK · -MK | Expansion module: 12 DI + 4 DO, RJ45 connection. |
| NDW-TL · -TL | Expansion module: 12 NTC + 4 leakage current inputs, RJ45 connection. |
| NDW-LCT45 | Leakage CT for NDW-TL, 45 mm window, one per channel. |
Need a solution for your project?
Contact us: we will select the equipment and network architecture to fit your requirements